SAFE RUNNING OF POWER CAPACITORS
A -
GENERAL
Every capacitor has limits in voltage, current, and
power handling capacity; these limits should not be
exceeded. For every CELEM capacitor a data sheet is
provided indicating the maximum rated voltage rms,
the maximum rated current and the maximum kVAr the
capacitor can handle. In selecting a capacitor for
an application, the highest operating voltage and
frequency should be chosen.
For example the CSM 150, 0.33 µF is rated at
700 volts rms, 250 Amperes and 150 kVAr. In examining
the graphs it can be seen that the capacitor is ideally
suited operating at frequencies between 150 to 250
kHz. This applies to any capacitors whose rated power
handling capacity lies in the frequency range as shown
on the graph.
If the capacitor is operated at reduced voltage or
frequency the kilovars may be computed from the following
relationship:
1. For reduced voltage
New kVAr = rated kVAr x (applied
volts / rated volts)²
2. For reduced frequency
New kVAr = rated kVAr x (applied
Hz / rated Hz)
3. The fundamental formula for kVAr
KVAr = V² x C (µF)
x 2 x p x F(kHz) x 10-3
B - POWER CAPACITORS
The evolution of semi-conductors runs parallel with
modern capacitors. Both are capable of handling large
amount of power in relatively small packages. For
correct operation, these components need suitable
cooling and be properly terminated. With CELEM water
cooled capacitors, the elements inside the capacitors
are arranged to be cooled equally and handle equal
power.
These capacitors will run trouble free for many years
if the required water flow is maintained.
When conduction cooled capacitors are used, 4 items
need to be addressed:
1. Cooling
The whole capacitor area should be in contact with
the heat sink. The capacitor area should be
covered with thermal conductive paste between the
capacitor and the heat sink. This is especially
required whenever the capacitor is working at its
maximum limits. The paste should be applied in the
same manner as with power semi-conductors.
2. Conduction losses
Most of the power capacitors are capable of supplying
several hundreds of Amperes each. If several capacitors
are connected to a common collector, it should be
remembered that due to the skin effect, if there is
not enough surface area, the portion of the bus bar
where the current is collected might get very hot;
even though it may be properly cooled.
3. Induction heating of the capacitors
If several conduction-cooled capacitors are assembled
between two bus bars, the ones located closest to
the output terminals may be induction heated. This
practice should be avoided. The correct way is to
mount the capacitors on each side of the bus bar or
built between the bus bars a low inductance path at
the current collector point (see drawing).
4. Stray inductance
Even if the capacitor bank is not connected directly
to the work coil, it is a good practice to avoid stray
inductance between the capacitor bank and the work
coil terminals.
It should be noted that the inductance at a connection
is proportional to is length, inversely proportional
to its width, and inversely proportional to the distance
between the bus bars.
C - CAPACITOR BANK
LOSSES
A capacitor bank consists of:
· Capacitors
· Connections between the capacitors and the
output terminals.
1. Capacitor losses:
Losses in the capacitors are extremely low, usually
= 5 x 10-4 x the reactive power
Therefore, for a 1000 kVAr capacitor bank, the losses
are approximately 0.5 kW.
2. Connection losses
In a properly constructed capacitor bank, the losses
will be approximately the same as that of the capacitor
bank, usually = 5 x 10-4 x the
reactive power
Therefore the total losses of the capacitor bank and
connections will be 1 x 10-3
of the reactive power
D - WATER FLOW REQUIRED
TO COOL A CAPACITOR BANK
Most of the capacitors available to-day employing
polypropylene as the dielectric will run safely up
to 90° Celsius.
The temperature rise on capacitors built by CELEM
is 40° Celsius above the temperature rise of the
heat sink and, therefore, the temperature of the cooling
water. In the worst-case condition, the temperature
of the cooling water is not expected to be above 40°
Celsius. Therefore, the maximum temperature rise allowed
for the water is 10° Celsius, thus the heat sink
temperature is 40 + 10 = 50° Celsius, and the
capacitor temperature will be 90° Celsius. This
is the maximum allowed temperature. In practice, however,
with cold water passing through the cooled heat sink
the capacitor temperature will not exceed 40°
Celsius.
As previously discussed, in a 1000 kVAr capacitor
bank; the total losses are 1 kW. Therefore, for a
10°Celsius rise (18°Fahrenheit) the water
flow required is:
in the CGS system LPM (litres per minute) = 14.36
x kW/°C = 1.44 LPM
in the ILS system GPM (gallons per minute) = 6.8
x kW/°F = 0.38 GPM
This of course is the minimum water flow required.
Whenever the capacitor bank is cooled in series with
the work coil it must be remembered that the losses
of the work coil are at least 10 times that of the
capacitor bank.
Therefore, the capacitor bank should be cooled first
followed by the work coil.
|